An 18-floor building with 126 meter positions — measured packet loss, retransmission strategy and gateway placement.

LoRa · 2026-09-18

An 18-floor apartment building with 126 meter positions — measured packet loss, retransmission strategy and gateway placement.

The client is an 18-floor apartment building with 126 meter positions scattered across service shafts. Meter reading was manual, once a month, with stale and noisy data. This note records what we actually measured.

Where to Put the Gateway

The first pitfall was gateway placement. We started with the gateway in the ground-floor power room: packet loss above floor 12 hit 40%.

Moving it to a 9th-floor corridor made the coverage radius symmetric and dropped packet loss below 3%.

Conclusion: in multi-story buildings, a mid-floor gateway beats both the rooftop and the basement.

Measured Data

Retransmission Strategy

Our strategy: stop once read, retry after 30 s if missed, at most 3 tries. Nodes still failing after 3 retries were almost always caused by metal meter-box shielding — extending the antenna with a short feeder cable on site solved it.

Meters are powered at DC 5 V from the meter bus, so power is not the bottleneck. On battery power, the reporting interval would need to stretch from 15 minutes to 6 hours to reach a 2-year service life.